Corrosion Authority

Meter Loading Diagnostics

What this page is for

These formulas help diagnose DVM meter loading error during pipe-to-electrolyte potential measurements. When the contact or external circuit resistance is high, the meter input resistance becomes part of a voltage-divider circuit and pulls the displayed reading toward zero (less negative) compared with the true polarized potential.

In practice, meter loading is most likely in dry soil, gravel, poor reference electrode contact, or other high-resistance measurement conditions. The formulas below are used to model the divider effect, estimate external resistance, correct the true potential from two readings, and calculate percent error.

Meter loading formulas

1) Meter loading (voltage divider)

\[ V_m = E_{true} \,\times\, \left(\frac{R_m}{R_m + R_{circ}}\right) \]
\(V_m\) = meter reading (loaded)
\(E_{true}\) = true polarized potential (no loading error)
\(R_m\) = meter input resistance
\(R_{circ}\) = external/contact (measurement circuit) resistance

2) Solve for external/contact resistance

\[ R_{circ} = R_m \,\times\, \left(\frac{E_{true}}{V_m} - 1\right) \]
\(R_{circ}\) = external/contact resistance
\(R_m\) = meter input resistance
\(E_{true}\) = true polarized potential
\(V_m\) = measured (loaded) meter voltage

3) Two-reading true-potential correction

\[ K = \frac{R_l}{R_h} \qquad\qquad E_{true} = \frac{V_h \,\times\, (1-K)} {1 - K \,\times\, \left(\frac{V_h}{V_l}\right)} \]
\(K\) = ratio of input resistances
\(R_l\) = lower meter input resistance
\(R_h\) = higher meter input resistance
\(V_l\) = measured voltage using \(R_l\)
\(V_h\) = measured voltage using \(R_h\)
\(E_{true}\) = corrected (true) polarized potential

Tip: If both readings are negative, \(\frac{V_h}{V_l}\) can be computed using signed values because the negatives cancel.

4) Percent error (magnitude)

\[ \%\text{Error} = \left| \frac{V_m - E_{true}}{E_{true}} \right| \,\times\, 100 \]
% Error = magnitude of loading error
\(V_m\) = measured (loaded) reading
\(E_{true}\) = true potential (corrected)

Practice problems

Practice 1: What causes DVM (meter loading) error?

When measuring pipe-to-electrolyte potential, the DVM displays a value that is less negative than expected.

What condition most directly causes meter loading error?

Reveal solution

Use (concept):

\[ V_m = E_{true} \,\times\, \left(\frac{R_m}{R_m + R_{circ}}\right) \]

Meter loading becomes significant when the external/contact resistance \(R_{circ}\) is high and approaches the meter input resistance \(R_m\). Then the divider fraction becomes noticeably less than 1 and the measured value is pulled toward 0 (less negative).

Answer: High external/contact resistance comparable to the meter input resistance.
Practice 2: Basic voltage divider relationship

True polarized potential \(E_{true}=-1.200\,\text{V}\). Meter \(R_m=10\,\text{M}\Omega\). External resistance \(R_{circ}=2\,\text{M}\Omega\).

What will the meter read (approx.)?

Reveal solution

Use:

\[ V_m = E_{true} \,\times\, \left(\frac{R_m}{R_m + R_{circ}}\right) \] \[ V_m = (-1.200) \,\times\, \left(\frac{10}{10+2}\right) = (-1.200) \,\times\, \left(\frac{10}{12}\right) = (-1.200) \,\times\, 0.8333 \approx -1.000\ \text{V} \]
Answer: -1.000 V (approx.)
Practice 3: Interpreting symptoms in the field

You switch from a 10 MΩ DVM to a 100 MΩ electrometer and the reading becomes noticeably more negative.

What is the best interpretation?

Reveal solution

Key idea:

Increasing \(R_m\) reduces loading error.

Reasoning:

If the reading becomes more negative when \(R_m\) increases, the earlier 10 MΩ reading was being pulled toward 0 by the divider effect, and the higher-impedance meter is closer to \(E_{true}\).

Answer: The 10 MΩ meter was loading the circuit; the higher-impedance meter reduced error.
Practice 4: Two-reading method requirement

You plan to use the two-reading true-potential correction method.

What must be different between the two measurements?

Reveal solution

Use (concept):

\[ K=\frac{R_l}{R_h} \qquad E_{true}=\frac{V_h \,\times\, (1-K)}{1-K \,\times\, \left(\frac{V_h}{V_l}\right)} \]

You must take two readings with two different meter input resistances (\(R_l\) and \(R_h\)) to create a solvable system.

Answer: Two different meter input resistances (\(R_l\) and \(R_h\)).
Practice 5: Calculating \(R_{circ}\) from one reading

A measurement gives \(V_m=-0.900\,\text{V}\) using \(R_m=10\,\text{M}\Omega\). You believe \(E_{true}=-0.950\,\text{V}\).

What is \(R_{circ}\) (approx.)?

Reveal solution

Use:

\[ R_{circ}=R_m \,\times\, \left(\frac{E_{true}}{V_m}-1\right) \] \[ R_{circ}=10 \,\times\, \left(\frac{-0.950}{-0.900}-1\right) =10 \,\times\, (1.0556-1) =10 \,\times\, 0.0556 =0.556\ \text{M}\Omega \]
Answer: 0.56 MΩ (approx.)
Practice 6: What reduces meter loading error most?

You are measuring pipe-to-soil potential in very dry/high-resistivity conditions.

Which action most directly reduces meter loading error?

Reveal solution

Use (concept):

\[ V_m = E_{true} \,\times\, \left(\frac{R_m}{R_m + R_{circ}}\right) \]

Reasoning:

Increasing \(R_m\) increases the divider fraction and moves \(V_m\) closer to \(E_{true}\).

Answer: Use a higher-input-impedance meter/electrometer.
Practice 7: When is loading error most likely?

Consider the relative sizes of \(R_m\) and \(R_{circ}\).

When is meter loading error most likely?

Reveal solution

Rule of thumb:

Loading error becomes significant when \(R_{circ}\) approaches \(R_m\).

Reasoning:

If \(R_m \gg R_{circ}\), then \(R_m/(R_m+R_{circ}) \approx 1\) and loading is minimal. If \(R_{circ}\) is large, the fraction drops and the reading is biased toward 0.

Answer: When contact/external resistance is high and approaches the meter input resistance.
Practice 8: Percentage error (magnitude)

True potential is \(-1.500\,\text{V}\). Meter reads \(-1.200\,\text{V}\) due to loading.

What is the magnitude of the percent error (approx.)?

Reveal solution

Use:

\[ \%\text{Error}= \left| \frac{V_m - E_{true}}{E_{true}} \right| \,\times\, 100 \] \[ \%\text{Error}= \left| \frac{-1.200-(-1.500)}{-1.500} \right| \,\times\, 100 = \left|\frac{0.300}{-1.500}\right| \,\times\, 100 = 0.20 \,\times\, 100 =20\% \]
Answer: 20% (magnitude)
Practice 9: Quick diagnostic check

You suspect loading error during a survey.

What quick check is most appropriate?

Reveal solution

Best check:

Repeat the measurement with a much higher input resistance meter/electrometer and observe whether the reading shifts more negative.

Why:

If \(V_m\) changes meaningfully as \(R_m\) changes, a voltage-divider loading error is strongly indicated.

Answer: Repeat with a much higher impedance meter and observe the change.
Practice 10: Defining \(K\) in the two-reading method

You are using the two-reading true-potential correction method.

How is \(K\) defined?

Reveal solution
\[ K=\frac{R_l}{R_h} \]

Where \(R_l\) is the lower meter input resistance and \(R_h\) is the higher meter input resistance.

Answer: \(K=R_l/R_h\).