What this page is for
These formulas cover several common pipe-to-soil potential calculations used in CP work, including temperature correction, meter loading, true potential correction, polarization shift, and common reference electrode conversions. The main goal is to recognize what the meter is actually reading, when a correction is needed, and how to interpret the result without mixing reference scales or mistaking IR drop for true polarization.
Pipe-to-soil potential formulas
1) Temperature correction (to 25°C)
\(K_t\) (CSE) ≈ +0.9 mV/°C
\(K_t\) (Ag/AgCl) ≈ −0.7 mV/°C (depends on fill solution)
2) Meter loading (voltage divider)
3) True potential from one reading
5) Two-meter true-potential method
Ag/AgCl potential depends on fill solution (for example, seawater vs saturated KCl), so always verify which reference value is being used before converting measured potentials from one scale to another.
Step-by-step method
- Identify the type of correction you need: temperature correction, loading correction, polarization shift, IR drop, or reference conversion.
- Confirm the reference electrode scale before comparing values or converting them.
- Keep units consistent throughout the calculation (mV vs V, MΩ vs Ω, and reference values in the same scale).
- Use the correct measured value for the situation, such as loaded meter reading, instant-off potential, native potential, or reference conversion value.
- Sanity-check the result so the direction of the correction makes physical sense.
Practice problems
A structure potential is measured as -865 mV with respect to a Copper/Copper Sulfate (CSE) electrode. The reference electrode temperature is 45°C. Calculate the corrected potential at the standard temperature of 25°C.
Reveal solution
Note: with a hot CSE, the pipe can appear more negative than the 25°C-corrected value.
You measure a potential of -820 mV using a CSE reference electrode in freezing conditions (-5°C). Calculate the corrected potential at 25°C. Does it meet the -850 mV criterion?
Reveal solution
\(-847\ \text{mV}\) is more positive than \(-850\ \text{mV}\), so it does not meet the criterion.
A potential of -800 mV is measured using a Silver/Silver Chloride electrode (sat. KCl). You need to report the value as CSE.
Assume: \(E_{SSC(sat\ KCl)} \approx +0.222\ \text{V vs SHE}\) and \(E_{CSE} \approx +0.316\ \text{V vs SHE}\).
Reveal solution
Note: Ag/AgCl potential depends on fill solution (seawater vs saturated KCl). This uses the saturated KCl value stated above.
You measure -900 mV on a structure. The meter has an input resistance \(R_m\) of 10 MΩ. The contact resistance \(R_{ext}\) is 2 MΩ. Calculate the true potential \(E_{true}\).
Reveal solution
Using Question 4, True = -1080 mV and Measured = -900 mV. Calculate the percentage error magnitude caused by loading.
Reveal solution
You measure the potential with two different input settings:
- Low impedance: \(R_l = 1\,\text{M}\Omega\), \(V_l = -650\,\text{mV}\)
- High impedance: \(R_h = 10\,\text{M}\Omega\), \(V_h = -800\,\text{mV}\)
Calculate the true potential \(E_{true}\).
Reveal solution
A pipeline survey shows:
- "On" potential: -1250 mV
- "Instant off" potential: -950 mV
What is the magnitude of the IR drop in the "on" reading?
Reveal solution
The "on" potential includes 300 mV of voltage drop through the electrolyte/coating path.
Determine if the 100 mV polarization criterion is met:
- Native potential: -550 mV
- "Instant off" potential: -700 mV
Calculate the polarization shift magnitude.
Reveal solution
Since \(150\ \text{mV} > 100\ \text{mV}\), the criterion is met by polarization shift.
A potential is measured as -1.000 V vs CSE. Convert to the SCE scale.
Hint: \(E_{CSE} \approx +0.316\ \text{V vs SHE}\), \(E_{SCE} \approx +0.244\ \text{V vs SHE}\).
Reveal solution
Sanity check: SCE is less positive than CSE, so the same structure appears less negative on SCE.
You calculate a polarized potential of -850 mV vs CSE. Convert to the SHE scale. Calculate \(V_{SHE}\).